- Reliable Electronic Operation
- No Moving Parts to Wear or Stick
- Controls Pump to Maintain Desired Liquid Level
- Can be Mounted Directly in Tank or in External Equalizing Line
- Remote Probe Mounts Any Distance from Control to Accommodate
Virtually Any Application
Specifications | Models 727 and 787 |
Max. Pressure | 250 PSI |
Power Consumption | 7 VA |
Switch Contacts | SPDT |
Switch Ratings | 10 A @ 240 VAC 1/3 hp @ 120 VAC 1/2 hp @ 240-600 VAC |
MODEL | VOLTAGE | DESCRIPTION/OPERATION | ||
LOW LEVEL CONTROL | ||||
727 | 120 VAC | Maintains level between probes. Energizes pump to refill tank when liquid level falls below bottom probe. De-energizes pump when liquid level reaches upper probe. Includes (1) EL1214-SV and (1) EL1214-RSV probe. | ||
HIGH LEVEL CONTROL | ||||
787 | 120 VAC | Maintains level between probes. Energizes pump to remove liquid from tank when the level reaches the upper probe. De-energizes pump when liquid level falls below bottom probe. Includes (1) EL1214-SV and (1) EL1214-RSV probes. |