- No Moving Parts in Boiler Water
- Controls Boiler Feed Pump
- Available with Water Column Type Body
- Accommodates Boilers to 250 PSI
[maxbutton id=”32″]
Specifications | Models 250 |
Primary Relay | 10 FLA, 60 LRA |
Pump Relay | 20 FLA, 120 LRA |
Switch Control | DPST |
Power Consumption | 13 VA |
MODEL | INCLUDES | DESCRIPTION/OPERATION |
PUMP CONTROL / CUT-OFF WITH AUTOMATIC RESET | ||
250 | Controller Model 250C Manifold (3) EL1214 Probes |
Operates boiler feed pump to maintain water level between middle and upper probes. Burner circuit contacts open if water drops below bottom probe. Automatically restarts burner on return of normal water level.
Same as Model 250 with water column body, tri-cock and gauge glass tappings. |
250WC | Controller Model 1214C-1 Manifold (3) EL1214 Probes |
PUMP CONTROL / CUT-OFF WITH TIME DELAY & MANUAL RESET | ||
LCFT-967 | Controller (for remote mounting) Model 1214 C-1 (3) EL1214 Probes |
Operates boiler feed pump to maintain water level between middle and upper probes. If water drops below bottom probe, the burner circuit contacts open after a 60 second delay. Locks-out burner circuit if water remains below bottom probe for 90 seconds. Manual reset will not lock-out from power interruptions. |